| description | Develop the backend simulation — device models (PV/load/AMI), the per-tick feeder solver, reading generation, telemetry sources, and FastAPI routers. Use when adding or changing how meters generate readings, how the grid solver computes voltages/flows/losses, how real telemetry overrides synthetic models, or how a new measurement/field surfaces through the API. (For editing .glm topology files themselves, use glm-topology-authoring instead.) |
Developing the simulation backend
The simulator runs an async tick loop: each tick generates per-meter readings with Python
device models, then runs an approximate feeder solver over the grid to derive bus voltages,
line flows, losses, and congestion. This skill maps the data flow and the safe extension
points. All paths are under src/smart_meter_simulator/.
For grid-model file edits (.glm buses/lines/loads/PV) use the glm-topology-authoring
skill — that's a different parser concern. This skill is about the Python simulation.
The tick data flow (read this first)
core/engine.py → SimulationEngine.tick() is the spine. One tick, in order:
_apply_telemetry(sim_time) — telemetry_source.poll() returns a frame of
{meter_id -> MeterTelemetry}. For each matched meter it sets one-shot attributes
manual_override_cons / manual_override_gen / manual_override_reactive_kvar and calls
meter.receive_frequency(...). Meters absent from the frame stay synthetic → partial
coverage is a hybrid run.
reading_manager.generate_all(...) — core/reading_manager.py. Calls
meter.update_weather() on every meter, then runs _generate_python_loop via
asyncio.to_thread (reading generation is CPU-bound — keep it off the event loop).
The loop reads each meter's override attrs, passes them to generate_reading, then
deletes the override attrs (that's what makes them one-shot) and stores last_reading.
It also looks up the meter's bus voltage from the previous tick (bus_voltages +
meter_to_bus) and feeds it in as grid_voltage_pu.
grid.update_grid_state(meters, readings) — core/grid_manager.py. Buckets each
reading's net load (kW) and reactive (kVAr) onto its bus, then solves.
_summarize_tick rolls totals into last_tick_summary; sim clock advances by interval.
So: readings drive the solver; the solver's voltages feed the next tick's readings. A
one-tick voltage lag is by design.
The engine is a process-global singleton — core/app_state.engine, created in lifespan.py.
Routers reach it via Depends(get_engine); there is no per-request state.
Where to make changes
A new measurement field on a reading
- Add the field to
EnergyReading in models/reading.py (it's a pydantic model; mind the
ge=/le= validators) and to to_telemetry_payload() if it should hit the API.
- Populate it in
devices/ami.py::SmartMeter.generate_reading — that's the single place a
reading is constructed. Note the round(...) + "key" in e_params guarding pattern.
- If it's a physics quantity, compute it in
core/meter_logic/electrical.py
(calculate_electrical_params) and gate it on the meter's measurement channels
(the "v"/"i"/"p"/"q" in channels checks). Channels come from
METER_TYPE_CHANNELS (config/channels.py) keyed by MeterType.
Device model behavior (generation / consumption)
- PV —
devices/solar.py. Real model is pvlib/PVWatts (_get_pvlib_generation_kw,
gated by cfg.pv_model_enabled); falls back to core/meter_logic/profiles.py:: calculate_solar_generation. Weather scales via _WEATHER_FACTORS. AR(1) noise via
self.last_noise — preserve that smoothing if you touch it.
- Load —
devices/load.py. Profile shape from profiles.calculate_consumption, then
ZIP voltage response (apply_zip_voltage_response: Z∝V², I∝V, P constant), clamped to
min_load_kw/max_load_kw. ZIP fractions come from config or per-meter config overrides.
- Inverter/droop controls live in
ami.py::generate_reading (over-voltage curtailment
above 1.05 pu) and electrical.py::apply_droop_control (frequency-watt, 50 mHz deadband).
There is no battery/EV/BESS model — meters are load + optional PV only.
The feeder solver
core/grid_manager.py has two solvers, tried in order inside update_grid_state:
- pandapower (
_run_pandapower) — full AC power flow, used only if pandapower is
importable and a pp_net was built (_build_pandapower_network runs at
initialize_network). Writes back vm_pu, line loading %, losses.
- DistFlow fallback (
_run_distflow) — pure-Python radial sweep over a networkx
BFS tree rooted at the substation. Always available; pandapower is optional.
Both write the same bus_voltages / line_flows / total_losses_kw state. If you add a
metric, populate it in both paths or the result depends on whether pandapower is installed.
Line names must stay consistent between the networkx edge, line_flows, and the pandapower
net.line.name (see the comment in _build_pandapower_network) or write-back silently misses.
Telemetry sources (drive meters from real data)
core/telemetry_source.py. Subclass TelemetrySource, implement poll(sim_time) -> Frame
(a {meter_id -> MeterTelemetry} dict), and register it in build_telemetry_source +
parse_telemetry_spec. Spec scheme mirrors topology: TELEMETRY_SOURCE=replay:<csv> /
reference-grid:<folder> / synthetic (default). Existing impls: ReplaySource (CSV,
hold-last-value), ReferenceGridReplaySource (CINELDI/MATPOWER p_load.csv/q_load.csv).
Meter ids must match the fleet — reference grids use reference_meter_id(bus_id).
A new API endpoint
routers/ — simulation_v1, meters_v1, grid_v1, mounted under /api/v1 by api_v1.py.
Handlers stay thin: engine = Depends(get_engine), mutate/read engine state, return a dict.
simulation_v1.py::update_environment is the model for live reconfiguration (weather,
grid_stress, hot-swapping topology). Keep business logic in the engine/managers, not handlers.
Conventions specific to this code
from __future__ import annotations at module top. black/isort (profile black, len 88).
- Read config only through
get_config() (config/settings.py, cached singleton). Per-meter
config dict values override global config where the device models check
config.get(key, get_config().key) — preserve that precedence.
- Reading generation must stay non-blocking — it runs under
asyncio.to_thread. Don't add
await into the device-model call path; don't do blocking I/O on the event loop.
- Overrides are one-shot attrs consumed-and-deleted each tick. Don't persist them on the meter.
- Keep new grid parsers/sources emitting the neutral shapes (
GridTopology, MeterTelemetry,
EnergyReading) rather than ad-hoc dicts.
Verify a change
PYTEST_ADDOPTS=--no-cov uv run pytest -q tests/test_telemetry_ingestion.py
uv run pytest -k <name> --no-cov
uv run cli --mode standalone --meters 20
uv run cli --mode validate-topology
uv run black src tests && uv run isort src tests && uv run flake8 src tests
Tests live in tests/ (e.g. test_glm_core_topology.py, test_telemetry_ingestion.py,
test_reference_grid_sources.py). Add new device/solver/source tests there; prefer
constructing a small GridTopology + a handful of SmartMeters and asserting on
engine.tick() output over mocking.