| description | Catalog of every configuration axis in Plenum — config.yaml add-on options, run.sh/backend environment variables, system_settings DB keys, ThermostatConfig fields, per-room settings, schedule/override fields — with defaults, units, validation guards, and UI location. Load when you need to know where a setting lives, what its default/bounds are, whether a value is stored in °F or as a delta, or when adding a new knob (config option, temperature field, or system flag) and need the parity checklist. |
Plenum configuration and flags
Every tunable in Plenum, layer by layer, with where it is stored, its default,
its guard, and where the user reaches it. All facts verified against the repo
at v0.22.1 (2026-07). Trust these tables only after running the re-verification
one-liners in Provenance if the repo has moved.
When NOT to use this skill
- How to run the add-on / docker / ports / backup →
plenum-run-and-operate.
- WHY a guard exists (deadband physics, short-cycling, dead-heading) →
hvac-zoning-reference.
- What CI gates a change must clear before merging a new knob →
plenum-change-control.
- The #231 write-boundary conversion contract itself →
plenum-architecture-contract (one-liner here: frontend sends raw display values; the backend converts at the write boundary via to_f/delta_to_f).
Jargon used below
- absolute temp: a real temperature; °C→°F uses
*9/5 + 32.
- delta temp: a difference (deadband, offset); °C→°F uses
*9/5 only — no 32 offset. Mixing these silently corrupts data.
- deadband: ±°F tolerance within which a room counts as "at target".
- overshoot: how far past the most demanding room's target the thermostat is set to keep the HVAC running.
- holdover: how long a presence-activated room stays active after last motion.
The universal invariant: every temperature is stored in °F in SQLite.
Conversion helpers live in smart_vent/backend/units.py (to_f, delta_to_f,
from_f, from_f_delta); routes.py imports them as _to_f etc. (CLAUDE.md
was corrected 2026-07-05 to say so — the import aliases are in routes.py, the
implementations in units.py.) Validation bounds are applied after
normalization to °F, per the lesson recorded in .jules/sentinel.md
(2026-05-05): validating the raw input before conversion is meaningless when
the unit varies. The canonical band for user-facing targets is 40–90 °F on
the internal °F value; setpoint clamps get 40–100 °F (verified in code, see
tables).
Layer 1 — Add-on options (smart_vent/config.yaml → run.sh)
Stored by the HA Supervisor in /data/options.json; read by run.sh via
bashio::config with an uppercase-env-var fallback for plain Docker (helper
get_config in run.sh). Parity between config.yaml options: and run.sh
is enforced by smart_vent/backend/tests/test_addon_config.py.
| Option | Schema | Default | Exported as | Notes |
|---|
ha_url | str | "" | HA_URL | Blank + supervisor → http://supervisor/core; blank + no supervisor → http://homeassistant.local:8123 |
ha_token | str | "" | HA_TOKEN | Blank → SUPERVISOR_TOKEN when available |
use_wss | bool | false | HA_USE_WSS | truthy set: 1/true/yes (parsed in ha_client.py) |
ssl_verify | bool | true | HA_SSL_VERIFY | |
timezone | str | "America/New_York" (config.yaml) / UTC (run.sh fallback) | TZ | Drives schedule evaluation (backend/tz.py reads TZ) |
temperature_unit | str | "" (auto-detect) | TEMPERATURE_UNIT | Non-empty F/C is a hard override lock in the scheduler; blank lets HA /api/config + last-known DB value decide. Do not default to F (#281) |
Ports/manifest facts (config.yaml): ingress on 8099, MCP on 9099
(both host-ports optional/blank by default), DATA_DIR: /config via the
environment: block, map: [data, addon_config:rw]. run.sh one-time
migrates flair.db/app.db from /data to $DATA_DIR. CI=true makes
run.sh self-kill after 10 s (smoke test).
Layer 2 — Environment variables the backend reads
Grep-verified across smart_vent/backend/ (excluding tests):
| Env var | Read in | Default | Purpose |
|---|
DATA_DIR | main.py, mcp_server.py | /data (backend) — but run.sh exports /config | SQLite app.db location |
PORT | main.py | 8099 | Web UI / API port |
MCP_PORT | main.py | 9099 | HTTP MCP server port |
HA_URL, HA_TOKEN | ha_client.py, mcp_tools/ha_entities.py | see Layer 1 | HA WebSocket/REST auth |
SUPERVISOR_TOKEN | ha_client.py | — | Injected by HA supervisor |
HA_USE_WSS | ha_client.py | false | wss:// vs ws:// |
HA_SSL_VERIFY | ha_client.py | true | TLS verification |
TZ | tz.py | — | Local timezone for schedules |
TEMPERATURE_UNIT | scheduler.py (_unit_override) | "" | Unit override lock (see Layer 1) |
CI | run.sh only | — | Smoke-test self-exit |
Frontend build-time: VITE_APP_VERSION — baked from config.yaml version:;
the value "CI" flips isCI in frontend/src/ci.tsx (frozen UI for E2E
goldens). Not a runtime knob.
Layer 3 — system_settings DB keys (key/value TEXT table)
Accessors: db.get_system_setting / db.set_system_setting
(smart_vent/backend/db.py ~line 2259). Exhaustive key list (grep-verified;
booleans stored as "1"/"0"):
| Key | Default | Set by | Read by | UI |
|---|
temperature_unit | "F" | scheduler startup (env override or HA detect) | scheduler _active_unit; everything reads unit via scheduler.get_temperature_unit() (sync), never DB directly | GET /api/settings; display-only |
unit_change_ack_required | "0" | scheduler per-tick _check_unit_change | GET /api/settings | UnitChangeBanner; dismiss POST /api/settings/ack-unit-change |
unit_change_acked_unit | "" | ack_unit_change() — records which HA unit was dismissed so the banner doesn't re-raise (#288) | scheduler | none (bookkeeping) |
system_enabled | "1" | POST /api/system/enabled | engine gate | master toggle in App.tsx header |
developer_mode | "0" | POST /api/system/dev-mode | scheduler + ha.dev_mode (suppresses real HA writes) | App header + DevMode.tsx page |
mcp_enabled | "0" | POST /api/system/mcp | MCP ASGI app per-request (returns 503 when off) | App header toggle |
vacation_mode_enabled | "0" | POST/DELETE /api/settings/vacation-mode | scheduler + engine | VacationModeModal / VacationModeBanner |
vacation_mode_return_at | "" | same | scheduler _check_vacation_expiry (auto-disables past return time) | same; return_at required, must be future ISO-8601 |
outside_temperature_entity_id | "" | PUT /api/settings/outside-temp-entity (validates entity exists in HA and is numeric) | cooling lockout (#209), pre-cool (#248), metrics | OutsideTempPicker on Thermostats page |
sensor_stale_after_min | 30.0 (SENSOR_STALE_AFTER_MIN, engine/cycle_engine.py:55) | PUT /api/settings/sensor-staleness — guard 1–1440 min | engine staleness guard (#211), /api/sensor-health | Thermostats page |
event_log_retention_days | "7" | POST /api/settings/log-retention — guard max(1, int(v)) | log trim job | Logs page |
cycle_log_retention_days | "30" | same | same | Logs page |
migration_holdover_timestamps_utc_v1 | — | one-shot migration sentinel (#65) | db.init_db | none |
migration_short_cycle_defaults_v1 | — | one-shot sentinel (#208 backfill: existing thermostats get runtime=10/off=5 min) | db.init_db | none |
The scheduler caches system_enabled / developer_mode / mcp_enabled /
vacation state in memory at startup and on reload_from_db(); routes read the
cached getters, never the DB.
Layer 4 — ThermostatConfig fields (smart_vent/backend/models.py, PK thermostat_entity_id)
Written by POST /api/thermostats and PUT /api/thermostats/{entity_id};
docs: docs/thermostat-settings.md, docs/safety.md. UI: Thermostats page
(SAFETY_FIELDS loop in frontend/src/pages/Thermostats.tsx, kind: "absolute_temp" | "delta_temp" | "other" drives the unit-label suffix).
Numeric safety fields are bounds-checked by _THERMO_NUMERIC_BOUNDS in
routes.py (#295) — non-numeric or negative values would crash/invert engine
tick arithmetic.
| Field | Default | Unit/kind | Guard (server-side) | Status |
|---|
name | "" | — | — | production |
default_temp | None | °F absolute, nullable (fallback presence target) | 40–90 °F post-conversion; null clears | production |
min_setpoint / max_setpoint | 60.0 / 85.0 | °F absolute | 40–100 °F post-conversion; min < max | production; hard clamp on every setpoint command |
deadband | 0.5 | °F delta | ≥ 0 | production |
overshoot_delta | 2.0 | °F delta | ≥ 0 | production |
max_vent_closed_min | 0 (off) | minutes | ≥ 0 | production safety valve |
cycle_timeout_hours | 3.0 | hours | > 0 (strict; UI input min=0.5) | production safety valve |
reconciliation_interval_min | 0 (off) | minutes | ≥ 0; docs say "should not exceed cycle_timeout×60" but that upper bound is advisory only — not enforced in code (engine just skips when ≤0) | production |
total_vents_count | None | count (smart + passive registers) | positive int; required at registration (#213); null → transitional "≥1 open" fallback + UI banner | production |
has_bypass_damper | False | bool | — | production; True disables the airflow floor |
min_open_vents_fraction | 0.333 | fraction | 0 < v ≤ 1 | production; airflow floor = ceil(total × fraction) |
vacation_hvac_mode | "single" | enum | "range" or "single" | production |
min_cycle_runtime_min | 0 (off; recommended 10) | minutes | ≥ 0 | production, short-cycle protection (#208) |
min_cycle_offtime_min | 0 (off; recommended 5) | minutes | ≥ 0 | production (#208) |
cooling_lockout_below_f | None (off) | °F absolute, nullable | converted via _to_f; needs the outside sensor (Layer 3) | production (#209) |
overflow_during_min_runtime | True | bool | — | production (#237); auto-off in vacation mode |
unavailable_abort_after_min | 5 | minutes | non-negative int; 0 = never abort (not recommended) | production (#267) |
Layer 5 — Per-room settings (Room in models.py; Rooms page modal)
| Field | Default | Unit/kind | Guard | Notes |
|---|
name, thermostat_entity_id | required | — | — | |
include_thermostat_sensor | False | bool | — | Count the thermostat's own temp in the room average |
system_wide_temp | None | °F absolute, nullable | 40–90 °F post-conversion | The room-level presence target; falls back to thermostat default_temp (docs/presence.md) |
presence_holdover_hours | 2.0 | hours | 0–8760; 0 disables presence activation for the room | |
temp_offset | 0.0 | °F delta | −20 to +20 °F post-conversion | Post-vent-close drift compensation (#86) |
deadband_override | None (inherit thermostat deadband) | °F delta, nullable | 0–10 °F post-conversion; null clears (#277) | Affects only this room's start/join-cycle vote |
ambient_suppression_enabled | False | bool | — | Pre-cool/pre-heat (#248), docs/precool-presence.md; inert without outside sensor |
ambient_suppression_mode | "any_presence" | enum | any_presence | off_schedule_only | |
ambient_suppression_min_differential | 5.0 | °F delta | ≥ 0 | Outside must be this far past target to coast |
ambient_suppression_deadband | 2.0 | °F delta | ≥ thermostat deadband only when feature enabled | Widened coasting band; engine clamps with max() anyway |
ambient_suppression_off_schedule_window_min | 60 | minutes | non-negative int | Only for off_schedule_only mode |
notes | "" | — | — | |
Sub-entities: sensors (sensor.*), vents (cover.* with per-vent
control_method ∈ open_close | set_position | set_tilt_position | toggle),
presence sensors (binary_sensor.*). A room may have zero vents —
monitor-only rooms are supported by design (docs/rooms-and-zones.md: "Zero
or more vents").
Layer 6 — Schedules and overrides
Schedule (Schedule in models.py; Schedules page; docs/schedules.md):
days_of_week (0=Mon), local start_time/end_time (overnight blocks
allowed), target_temp (°F absolute, guard 40–90 °F post-conversion), plus
lifecycle (#359): enabled (default True — False "parks" the block, sweeps
never delete) and expires_at (naive local wall-clock datetime, null =
never; matches <input type="datetime-local">). Rules verified in
routes.py: overlap is rejected only between enabled blocks; an enabled
block cannot be created already-expired; the scheduler's
schedule_expiry_sweep job auto-disables expired blocks but lets a
currently-running block finish first. POST …/schedules/{id}/copy clones
days/times/target to other rooms — copies are enabled+never-expiring, and a
conflicting copy is created disabled with status
created_disabled_conflict.
Room override (POST /api/rooms/{room_id}/override): target_temp
(40–90 °F post-conversion) + duration_hours (default 2.0, guard 0–8760).
Priority: override > schedule > presence holdover.
The temperature-field registry (3-file lockstep)
TEMPERATURE_FIELDS in routes.py (~line 243) is the Python source of truth
for every body key converted at the write boundary. Kinds: absolute,
absolute_nullable, delta, delta_nullable. Current entries: default_temp,
min_setpoint, max_setpoint, deadband, overshoot_delta,
cooling_lockout_below_f, system_wide_temp, temp_offset,
deadband_override, ambient_suppression_min_differential,
ambient_suppression_deadband, target_temp. Mirrored in
e2e/tests/temperature-fields.ts; parity + // @covers: tags enforced by
smart_vent/backend/tests/test_temperature_field_parity.py.
ADD-A-KNOB checklists
Before touching anything, load plenum-change-control for gating/evidence.
Remember the CLAUDE.md 100% rule: every backend tunable gets a UI control
in the same change.
A. New config.yaml option
- Add to
options: AND schema: in smart_vent/config.yaml.
- Add a
get_config '<key>' '<default>' read + export <UPPER_KEY>=… in smart_vent/run.sh (the parity test greps for bashio::config '<key>' usage — test_addon_config.py fails otherwise).
- Read the env var in the backend (
os.environ.get) with the same default.
- Verify:
cd smart_vent && python -m pytest backend/tests/test_addon_config.py -q.
B. New temperature field on a write boundary
(Gates and reviewer evidence: plenum-change-control §2.1; parity-rule
mechanics and failure texts: plenum-validation-and-qa §5. This checklist is
the catalog-side companion, not the owner.)
- Backend: convert with
_to_f (absolute) or _delta_to_f (delta) from backend/units.py; validate the °F value after conversion (40–90 °F for user targets, per .jules/sentinel.md); pick nullable semantics deliberately.
- Register in
TEMPERATURE_FIELDS in routes.py with the right kind — a wrong absolute/delta kind silently corrupts data.
- Register in
e2e/tests/temperature-fields.ts (field, kind, ui, endpoints).
- If
ui: true: add a round-trip test in e2e/tests/temperature-units.spec.ts tagged // @covers: <field>.
- Frontend form: init via
toDisplay/toDisplayDelta, submit the raw display value — never toStorage on outgoing payloads (#231; contract owned by plenum-architecture-contract).
- Tests:
TestToF-style unit test + a Celsius-mode integration test (set client.app["scheduler"]._active_unit = "C", restore in finally).
- UI change ⇒ regenerate both
-Fahrenheit- and -Celsius- E2E goldens (see CLAUDE.md pitfall 8).
- Verify:
cd smart_vent && python -m pytest backend/tests/test_temperature_field_parity.py -q.
C. New system_settings flag (mirror the mcp_enabled pattern — verified in scheduler.py:256-267)
- Scheduler: private cached field (
self._flag), loaded in startup and reload_from_db(); sync getter get_flag(); async set_flag() that (a) updates the cache, (b) db.set_system_setting(...) as "1"/"0", (c) logs, (d) broadcasts a WS event flag_changed via self._broadcast if set. If the flag affects HVAC behavior, also call _reset_and_reevaluate(...) (see set_dev_mode/set_vacation_mode).
- Routes: GET exposure (piggyback
/api/system/status or /api/settings) + a POST setter that calls the scheduler setter and emit(...)s an event-log entry. Every route needs @docs + @response_schema (enforced by test_api_spec_enforcement.py).
- Frontend:
api.ts functions, a UI control (App header toggle for system-level flags), and a listener for the WS *_changed event to keep the UI live (see mcp_enabled handling in App.tsx).
- Tests: integration test toggling via the API and asserting persistence + broadcast.
Provenance and maintenance
Facts date-stamped 2026-07, v0.22.1. Re-verification one-liners (run from repo root):
- Layer 1:
cat smart_vent/config.yaml ; grep -n "get_config\|export" smart_vent/run.sh
- Layer 2:
grep -rn "os.environ\|os.getenv" smart_vent/backend/ --include="*.py" | grep -v tests
- Layer 3 keys:
grep -rhoE '(get|set)_system_setting\([^,]+, "[a-z_]+"' smart_vent/backend/ --include="*.py" | grep -oE '"[a-z_]+"' | sort -u
- Layer 3 defaults:
grep -n "SENSOR_STALE_AFTER_MIN" smart_vent/backend/engine/cycle_engine.py ; grep -n "retention_days" smart_vent/backend/api/routes.py
- Layer 4/5/6 fields+defaults:
sed -n '35,230p' smart_vent/backend/models.py
- Guards:
grep -n "_temp_range_error\|_THERMO_NUMERIC_BOUNDS\|40 <=\|8760\|1440" smart_vent/backend/api/routes.py
- Registry:
sed -n '243,263p' smart_vent/backend/api/routes.py ; cat e2e/tests/temperature-fields.ts
- mcp_enabled pattern:
sed -n '237,290p' smart_vent/backend/scheduler.py
- Parity tests:
cd smart_vent && python -m pytest backend/tests/test_addon_config.py backend/tests/test_temperature_field_parity.py -q (needs pip install ".[dev]"; not executed while authoring this skill — deps not verified installed)
Volatile line numbers cited (routes.py ~243, scheduler.py ~256, cycle_engine.py:55, db.py ~2259) will drift; the greps above re-locate them.