원클릭으로
parse-csv
Specialized instructions for parsing and extracting device information from BACnet filtered CSV files.
Codex 또는 Claude로 설치 이 Prompt를 복사해 Codex, Claude 또는 다른 어시스턴트에 붙여 넣으면 Skill 페이지를 검토하고 설치를 진행할 수 있습니다.
메뉴
Specialized instructions for parsing and extracting device information from BACnet filtered CSV files.
Codex 또는 Claude로 설치 이 Prompt를 복사해 Codex, Claude 또는 다른 어시스턴트에 붙여 넣으면 Skill 페이지를 검토하고 설치를 진행할 수 있습니다.
MUST READ before writing or modifying ADK agent code. ADK API quick reference for Python — agent types, tool definitions, orchestration patterns, callbacks, and state management. Includes an index of all ADK documentation pages. Do NOT use for creating new projects (use adk-scaffold).
MUST READ before deploying any ADK agent. ADK deployment guide — Agent Engine, Cloud Run, GKE, CI/CD pipelines, secrets, observability, and production workflows. Use when deploying agents to Google Cloud or troubleshooting deployments. Do NOT use for API code patterns (use adk-cheatsheet), evaluation (use adk-eval-guide), or project scaffolding (use adk-scaffold).
ALWAYS ACTIVE — read at the start of any ADK agent development session. ADK development lifecycle and mandatory coding guidelines — spec-driven workflow, code preservation rules, model selection, and troubleshooting.
MUST READ before running any ADK evaluation. ADK evaluation methodology — eval metrics, evalset schema, LLM-as-judge, tool trajectory scoring, and common failure causes. Use when evaluating agent quality, running adk eval, or debugging eval results. Do NOT use for API code patterns (use adk-cheatsheet), deployment (use adk-deploy-guide), or project scaffolding (use adk-scaffold).
MUST READ before setting up observability for ADK agents or when analyzing production traffic, debugging agent behavior, or improving agent performance. ADK observability guide — Cloud Trace, prompt-response logging, BigQuery Agent Analytics, third-party integrations, and troubleshooting. Use when configuring monitoring, tracing, or logging for agents, or when understanding how a deployed agent handles real traffic.
MUST READ before creating or enhancing any ADK agent project. Use when the user wants to build a new agent (e.g. "build me a search agent") or enhance an existing project (e.g. "add CI/CD to my project", "add RAG").
SOC 직업 분류 기준
| name | parse_csv |
| description | Specialized instructions for parsing and extracting device information from BACnet filtered CSV files. |
This skill provides a specialized knowledge base and prompt structure for LLMs to understand and extract information from BACnet-exported CSV files.
BACnet CSV exports typically follow this column schema:
| Column | Description | Example |
|---|---|---|
| bacnet | Unique point ID (Controller.Object) | 2500.AI11 |
| nom | Descriptive name (often in French) | VITESSE RET. No.1A |
| valeur | Current real-time value | 4,08806 A |
| unit | Unit of measurement | Amperes |
Understanding the suffix in the bacnet column is critical for identifying the "nature" of the data point.
| Suffix | Full Name | Description |
|---|---|---|
| .AI | Analog Input | Measured physical values (Temp, Pressure, Speed). |
| .AO | Analog Output | Control signals (0-100% modulation). |
| .AV | Analog Value | Internal setpoints or calculation buffers. |
| .BI | Binary Input | Physical status (Running/Stopped, Fault). |
| .BO | Binary Output | Physical commands (Start/Stop, Open/Close). |
| .BV | Binary Value | Internal software flags or logical triggers. |
| .CO | Control Loop | PID loop parameters (modulation logic). |
| .PG | Program | Control sequences and logic blocks. |
| .SCH | Schedule | Weekly or daily operation timers. |
| .TL | Trend Log | Historical data collection points. |
The nom column contains specific abbreviations. Use this mapping for extraction:
| French | English Equivalent | Context |
|---|---|---|
| RET. / RETOUR | Return | Return Air / Return Pipe |
| ALIM. / ALIMENTATION | Supply | Supply Air / Supply Pipe |
| MEL. / MELANGE | Mixing | Mixing Box / Outside Air Mixing |
| EVAC. / EVACUATION | Exhaust | Exhaust Air / Evacuation |
| TEMP. | Temperature | Thermal measurement |
| PRES. / STAT. | Pressure / Static | Airflow or Hydraulic pressure |
| HUMI. / HUM | Humidifier | Humidity control |
| SERP. / ELECT. | Coil / Electric | Electric Coil |
| SERP. / REF. | Coil / Cooling | Refroidissement / Cooling Coil |
| ELECT. | Electric | Electrical heating/power |
| P.A.F | Fresh Air Inlet | Prise d'Air Frais |
| MOD. | Modulation | Analog control (0-100%) |
| DRIVE | VFD | Variable Frequency Drive |
| PC. / P.C. | Setpoint | Point de Consigne |
| FAUTE | Fault | 0 = Active Fault, 1 = Normal |
| VENT. | Fan | Ventilateur |
| A/D | Start/Stop | Arrêt/Départ |
| STATUT DIG | Digital Status | Logical On/Off state |
| CALCULS / CTRL | Logic / Control | Control Program points |
Golden Rule: When extracting a device, do not just look for the name. Look for the Logical Grouping. Devices are usually grouped by a suffix like 1A, 1E, or 1R.
EVAC).nom column for the keyword.1E).1E)?.PG) that governs the device?.BI/.BO) correctly identified as start/stop or status?.AV) included for all modulation points (.AO)?