| description | Set up anti-surge recycle control for a centrifugal compressor in NeqSim, including compressor-chart generation, steady-state AntiSurgeRecycleCalculator use, dynamic AntiSurgeController PI control, and CompressorAntiSurgeApplication topology binding for hot/cold recycle valves and speed runback. USE WHEN: a task needs to protect a NeqSim compressor from surge with a recycle (spill-back) loop and a compressor performance chart is either supplied or must be generated. |
| last_verified | 2026-07-02 |
| requires | {"python_packages":[],"java_packages":["neqsim"],"env":[],"network":false} |
Compressor Anti-Surge Recycle Setup
This skill explains how to protect a centrifugal compressor against surge in a
NeqSim ProcessSystem by adding a recycle (spill-back) loop. It covers the
preferred steady-state helper (AntiSurgeRecycleCalculator), the dynamic
reverse-acting PI controller (AntiSurgeController), and the application-level
supervisor (CompressorAntiSurgeApplication) that can bind directly to real
NeqSim topology objects such as a compressor, hot recycle valve, cold recycle
valve, cooler, mixer, recycle blocks, and ProcessSystem. It also explains how
to auto-generate a compressor chart with surge and stonewall curves when no
vendor chart is available, because every anti-surge option needs a surge limit
to act against.
The pure-Python helper (AntiSurgeRecycleModel) is an educational planning aid
that mirrors NeqSim's proportional anti-surge step so an agent can pre-estimate
the recycle flow and decide whether a chart must be generated first. Real
control design must use the validated NeqSim equipment classes below and a
qualified rotating-equipment review (API 617 / API 692).
When to Use
Use this skill when:
- A NeqSim compressor operating point can fall to the left of its surge line at
low throughput (turndown, start-up, trips) and needs recycle protection.
- You must build the anti-surge recycle topology (surge curve, recycle stream,
discharge splitter or recycle branch, anti-surge valve,
Recycle, and
optional cooler/mixer).
- You need an executable dynamic application model where
CompressorAntiSurgeApplication writes hot/cold recycle valve openings and
optional compressor speed runback to real NeqSim units.
- No vendor compressor chart is provided and a chart with surge and
stonewall curves must be generated from the compressor's design point.
- You want a screening estimate of the recycle flow required to keep the
compressor off surge before running the full simulation.
Do not use this skill as a substitute for vendor performance maps, anti-surge
controller tuning, dynamic surge/transient analysis, or rotating-equipment
design review.
Inputs
- Compressor inlet (suction) volumetric flow at the operating point (m3/h).
- Surge-limit flow at the operating head and speed (m3/h). When no vendor chart
is available, this comes from the generated surge curve.
- Whether a vendor compressor chart is provided (
chart_provided).
- Existing recycle flow, if any (m3/h).
- For chart generation: a design speed, the number of speed lines, and
optionally impeller diameter / number of stages for advanced corrections.
Outputs
needs_chart_generation — whether a chart must be generated before control.
in_surge — whether the operating point is at or below the surge flow.
surge_margin_fraction — (inlet_flow - surge_flow) / surge_flow.
recommended_recycle_flow — screening recycle flow to add at suction (m3/h).
total_suction_flow — inlet flow plus recommended recycle (m3/h).
recycle_warning — ok, recycle, or surge.
- Assumptions and limitations.
Engineering Method
A centrifugal compressor surges when the inlet volumetric flow drops below the
surge flow at the current head/speed. Anti-surge control opens a recycle line
from discharge back to suction to keep the total suction flow above the
surge limit plus a margin.
For steady-state recycle sizing and initialization, prefer
AntiSurgeRecycleCalculator for a charted compressor. It runs the compressor,
checks natural inlet flow against the surge-control line, and iterates a cooled
recycle stream until the target distance-to-surge margin is met. Use the older
splitter-based Calculator / AntiSurgeCalculator pattern only when you need
to reproduce an existing flowsheet that already uses a discharge splitter.
The legacy splitter-based topology is:
- A surge curve on the compressor chart provides the surge flow versus head.
- A low-flow recycle stream is added into the compressor suction.
- A splitter on the compressor discharge creates a forward branch
(
getSplitStream(0)) and a recycle branch (getSplitStream(1)).
- An anti-surge
Calculator (legacy name-prefix API) or typed
AntiSurgeCalculator reads the compressor and writes the splitter recycle
flow each iteration. Internally it compares the inlet flow to the surge flow:
far from surge (inlet_flow > 1.2 * surge_flow) it drives recycle to a
minimum; otherwise it adds a proportional, capped step
0.5 * (surge_flow - inlet_flow) to the recycle branch.
- An anti-surge valve on the recycle branch drops the discharge pressure
back to suction pressure.
- A
Recycle unit closes the loop, feeding the valve outlet back into the
placeholder suction recycle stream.
Generating a Compressor Chart When None Is Given
The anti-surge loop needs a surge limit, so if no vendor chart exists a chart
must be generated first. NeqSim builds a chart from the compressor's design
operating point and automatically populates both the surge curve and the
stonewall curve:
Compressor.generateCompressorChart("normal curves", numberOfSpeeds) builds a
multi-speed chart whose lowest-flow points form the surge curve and whose
highest-flow points form the stonewall curve.
CompressorChartGenerator gives finer control (chart type, Reynolds/Mach
corrections, multistage surge correction, impeller diameter) and also returns
a chart with surge and stonewall curves attached.
After generation, the surge flow at the operating head is available through
Compressor.getSurgeFlowRate() and the distance to surge through
Compressor.getDistanceToSurge().
The AntiSurgeRecycleModel mirrors step 4 so you can estimate the recycle flow
and flag whether chart generation (needs_chart_generation) is required before
wiring the loop.
Python Usage Pattern
Screening estimate of the recycle flow (no NeqSim required):
from compressor_antisurge_recycle import AntiSurgeRecycleModel
model = AntiSurgeRecycleModel()
plan = model.plan(
inlet_flow=4200.0,
surge_flow=5000.0,
chart_provided=True,
current_recycle=0.0,
)
print(plan.recommended_recycle_flow, plan.recycle_warning)
Generate a compressor chart (with surge and stonewall curves) when none is
given, using NeqSim through the neqsim package:
from neqsim import jneqsim
compressor.setSpeed(8000.0)
compressor.run()
compressor.generateCompressorChart("normal curves", 5)
chart = compressor.getCompressorChart()
surge_flow = compressor.getSurgeFlowRate()
distance_to_surge = compressor.getDistanceToSurge()
Finer control with the generator (optional corrections):
from neqsim import jneqsim
generator = jneqsim.process.equipment.compressor.CompressorChartGenerator(compressor)
generator.setChartType("interpolate and extrapolate")
generator.enableAdvancedCorrections(numberOfStages)
chart = generator.generateCompressorChart("normal curves", 5)
compressor.setCompressorChart(chart)
Wire the anti-surge recycle loop (generic data, after a chart exists):
from neqsim import jneqsim
splitter_pkg = jneqsim.process.equipment.splitter
valve_pkg = jneqsim.process.equipment.valve
util_pkg = jneqsim.process.equipment.util
suction_pressure = compressor.getInletStream().getPressure("bara")
recycle_gas = compressor.getInletStream().clone()
recycle_gas.setName("anti surge recycle gas")
recycle_gas.setFlowRate(1.0, "kg/hr")
recycle_gas.run()
process.add(recycle_gas)
gas_splitter = splitter_pkg.Splitter("anti surge splitter", compressor.getOutletStream(), 2)
gas_splitter.run()
process.add(gas_splitter)
anti_surge_calc = util_pkg.Calculator("anti surge calculator 1")
anti_surge_calc.addInputVariable(compressor)
anti_surge_calc.setOutputVariable(gas_splitter)
process.add(anti_surge_calc)
anti_surge_valve = valve_pkg.ThrottlingValve("anti surge valve", gas_splitter.getSplitStream(1))
anti_surge_valve.setOutletPressure(suction_pressure, "bara")
anti_surge_valve.run()
process.add(anti_surge_valve)
recycle = util_pkg.Recycle("recycle anti surge")
recycle.addStream(anti_surge_valve.getOutletStream())
recycle.setOutletStream(recycle_gas)
recycle.setTolerance(1e-2)
process.add(recycle)
process.run()
The forward process continues on gas_splitter.getSplitStream(0).
Preferred steady-state helper for a charted compressor:
AntiSurgeRecycleCalculator calc = new AntiSurgeRecycleCalculator(compressor, suctionStream);
calc.setSurgeControlMargin(0.10);
calc.setRecycleCoolerTemperature(35.0, "C");
AntiSurgeRecycleCalculator.Result result = calc.solve();
Dynamic Anti-Surge Control (AntiSurgeController)
The Calculator-driven loop above is a steady-state recycle solver. For a
dynamic (transient) anti-surge response, NeqSim provides a dedicated
reverse-acting PI controller, AntiSurgeController
(neqsim.process.controllerdevice.AntiSurgeController), that reads
Compressor.getDistanceToSurge() and drives a recycle ThrottlingValve open as
the margin falls below the set point, then closes it again on recovery.
from neqsim import jneqsim
controllerdevice = jneqsim.process.controllerdevice
asc = controllerdevice.AntiSurgeController("anti-surge", compressor, recycle_valve)
asc.setSurgeMarginSetPoint(0.10)
asc.setProportionalGain(400.0)
asc.setIntegralTime(20.0)
asc.setOpeningRange(0.0, 100.0)
asc.setActive(True)
recycle_valve.addController("anti-surge", asc)
Control law each transient step: error = setPoint - distanceToSurge,
integral += Kp/Ti * error * dt, opening = clamp(Kp*error + integral) with
anti-windup. A reproducible benchmark,
neqsim.process.util.scenario.AntiSurgeDynamicBenchmark, drives the real
controller against a transparent first-order gas-path surrogate
(m_next = m - disturbance*dt + authority*(opening/100)*dt) and is the preferred
way to verify or tune the control law without solver fragility.
Critical gotchas when building a full dynamic recycle flowsheet:
- A fixed-factor
Splitter (setSplitFactors([0.97, 0.03])) pins the recycle
fraction in dynamic mode, so the anti-surge valve has no authority over the
actual recycle flow — it can reach 100% open with no effect. Let the recycle
flow be set by the valve (Cv/resistance), or keep the steady-state
Calculator pattern.
- Once the operating point crosses left of the surge line,
getDistanceToSurge() clamps at -1.0 and the steady solver cannot recover;
a flowsheet driven into deep surge will not self-heal even after the inlet is
reopened. Apply gradual/ramped disturbances and keep the machine off deep surge.
- Aggressive proportional gain can slam the recycle valve to minimum opening,
starve a stream, and trigger an SRK flash
NaN
(PhaseSrkEos:molarVolume ... NaN). Keep gains moderate.
Dynamic controller tuning and transient surge analysis still require qualified
rotating-equipment review (API 617 / API 692).
Application-Level Dynamic Topology Binding
For realistic dynamic studies with coordinated pressure, speed, hot recycle, and
cold recycle behavior, use CompressorAntiSurgeApplication. It is a
deterministic supervisory scan layer that can write directly to real NeqSim
objects and then advance the bound process one transient step.
CompressorAntiSurgeApplication application = new CompressorAntiSurgeApplication("export compression");
CompressorAntiSurgeApplication.StageApplication stage = application.addStage("K-101");
CompressorAntiSurgeApplication.TopologyBinding binding = stage.bindTopology(
process,
compressor,
hotRecycleValve,
coldRecycleValve,
recycleCooler,
suctionMixer,
hotRecycle,
coldRecycle);
binding.enableSpeedControl(95.0, 25.0, 8500.0, 12500.0, 150.0);
application.setRunningMode();
application.runDynamicStep(null, 0.25);
When the scan input is null, the stage reads the bound compressor margin and
inlet flow where available, falls back to the stage design basis where needed,
writes the hot and cold recycle valve openings, applies the optional compressor
speed command/runback, and advances the bound ProcessSystem with
runTransient(). Keep Recycle blocks algebraic unless the specific class has
transient inventory support; the valve, compressor, cooler, mixer, and any
volume-capable equipment carry the dynamic response.
CompressorAntiSurgeApplication is still a simulation and advisory layer. Its
certification status remains NOT_CERTIFIED_FOR_PROTECTION; use it for
engineering studies, training, digital twins, and commissioning evidence, not as
a certified machinery-protection package.
Validation Checklist
- The compressor has a chart with an active surge curve before the loop runs;
if not, generate one and confirm
getSurgeCurve().isActive() is true.
- For steady-state recycle initialization, use
AntiSurgeRecycleCalculator when
practical; if using the legacy splitter path, the anti-surge Calculator name
starts with "anti surge calculator" or the typed AntiSurgeCalculator is
used.
- For the legacy splitter path, the
Calculator input is the Compressor and
the output is the discharge Splitter.
- The anti-surge valve sits on
getSplitStream(1) and drops to suction pressure.
- The
Recycle outlet stream is the placeholder suction recycle stream.
- After
process.run(), the total suction flow exceeds the surge flow plus the
intended margin (getDistanceToSurge() is positive).
- Recycle convergence tolerance is set (for example
setTolerance(1e-2)).
- For
CompressorAntiSurgeApplication topology binding, hot/cold recycle valves
are real ThrottlingValve units, speed-control limits are bounded, and
runDynamicStep(...) is used only after the process has a converged initial
state.
Common Mistakes
- Naming the legacy calculator anything that does not start with
"anti surge calculator" — the legacy anti-surge logic then never triggers.
- Wiring the anti-surge valve to the forward branch
getSplitStream(0) instead
of the recycle branch getSplitStream(1).
- Running the loop without a surge curve, so there is no surge flow to compare
against (generate a chart first when no vendor chart is given).
- Using a zero or negative placeholder recycle flow that the
Recycle cannot
converge from; start from a small positive flow (for example 1 kg/hr).
- Reading the surge flow at the wrong head or speed — the surge flow must match
the operating head and speed.
- Treating the generated chart as a vendor-validated map; generated charts are
estimates for modelling, not design certification.
- For dynamic studies, leaving a fixed-factor
Splitter on the recycle branch so
the AntiSurgeController valve has no authority over the recycle flow.
- Driving a dynamic recycle flowsheet straight into deep surge, where
getDistanceToSurge() clamps at -1.0 and the steady solver cannot recover.
Limitations
- Screening logic only; it does not tune an anti-surge controller or set
recycle valve
Cv, response time, or surge control line offset.
- The Python helper does not perform dynamic surge, ESD, or transient recycle
analysis; for dynamic response use NeqSim's
AntiSurgeController /
AntiSurgeDynamicBenchmark under qualified review.
- Generated compressor charts are model estimates, not vendor performance maps.
- It does not replace API 617 / API 692 rotating-equipment design and review.
- Results require qualified human review before any design or operating use.
Related NeqSim Functionality
neqsim.process.equipment.compressor.Compressor —
generateCompressorChart(...), getCompressorChart(),
getSurgeFlowRate(), getDistanceToSurge(), setSpeed(...).
neqsim.process.equipment.compressor.CompressorChart —
getSurgeCurve(), getStoneWallCurve(), generateSurgeCurve(),
generateStoneWallCurve(), checkStoneWall(...).
neqsim.process.equipment.compressor.CompressorChartGenerator —
setChartType(...), enableAdvancedCorrections(...),
generateCompressorChart(...).
neqsim.process.equipment.compressor.AntiSurgeRecycleCalculator — preferred
steady-state recycle helper for charted compressors
(setSurgeControlMargin, setRecycleCoolerTemperature, solve).
neqsim.process.equipment.compressor.CompressorAntiSurgeApplication —
application-level supervisor with StageApplication.bindTopology(...),
TopologyBinding.enableSpeedControl(...), scan(...), and
runDynamicStep(...) for direct writeback to real hot/cold recycle valves and
compressor speed.
neqsim.process.equipment.splitter.Splitter — discharge split into forward
and recycle branches.
neqsim.process.equipment.util.Calculator — steady-state anti-surge engine
(runAntiSurgeCalc) triggered by the "anti surge calculator" name prefix.
neqsim.process.controllerdevice.AntiSurgeController — dynamic reverse-acting
PI controller on getDistanceToSurge() driving a recycle valve
(setSurgeMarginSetPoint, setProportionalGain, setIntegralTime,
setOpeningRange, setActive).
neqsim.process.util.scenario.AntiSurgeDynamicBenchmark — reproducible
surrogate benchmark for verifying/tuning the dynamic control law.
neqsim.process.equipment.valve.ThrottlingValve — anti-surge recycle valve.
neqsim.process.equipment.util.Recycle — closes the recycle loop.
The total_suction_flow (net forward flow + recycle) computed here is the
actual compressor throughput. When you go on to compute polytropic
head/efficiency or shaft power from measured conditions, use this actual
throughput — not the metered net/export flow. Using net flow while the recycle is
open understates suction volume and power and mis-locates the operating point on
the surge map (a common error when diagnosing compressor degradation at
turndown).
In Python these classes are reachable through the neqsim package (for example
from neqsim import jneqsim).