| name | neqsim-flare-radiation-screening |
| version | 0.1.0 |
| description | Educational flare thermal-radiation screening using the public API 521 / API 537 point-source equation. USE WHEN: a task needs a public, screening-level estimate of radiant heat flux at a distance from a flare and a check against allowable radiation limits before detailed flare and radiation design. |
| last_verified | 2026-06-18 |
| requires | {"python_packages":[],"java_packages":[],"env":[],"network":[]} |
Flare Radiation Screening
Use this skill for public, educational flare thermal-radiation screening. It estimates radiant heat flux at a distance from a flare using the open API 521 / API 537 point-source model and compares it to common allowable limits so an agent can decide whether a detailed flare-radiation study is needed.
When to Use
- When a user asks how far personnel or equipment must be from a flare for a given relief rate.
- When an agent needs a quick radiation triage to scope a flare or relief study.
- When examples must run without confidential flare designs, vendor tip data, or company radiation criteria.
Inputs
mass_flow: flared mass flow in kg/s.
heat_of_combustion: lower heating value of the flared gas in MJ/kg.
distance: distance from the flame center to the receptor in m.
fraction_radiated: fraction of heat radiated F, default 0.2.
transmissivity: atmospheric transmissivity, default 1.0.
allowable_flux: allowable radiant flux in kW/m2, default 6.31 (API 521 limit for a few seconds of exposure).
Outputs
total_heat_release_kw: total combustion heat release Q.
radiant_heat_flux_kw_m2: radiant flux at the receptor.
allowable_flux_kw_m2: the supplied allowable flux.
flux_ratio: ratio of computed flux to allowable flux.
radiation_warning: ok, watch, or high.
assumptions: public assumptions used by the placeholder model.
Engineering Method
The Python class FlareRadiationModel uses the open API 521 / API 537 point-source equation only:
- the total heat release uses
Q = mass_flow * heat_of_combustion.
- the radiant flux uses
q = tau * F * Q / (4 pi r^2), treating the flame as a single point source.
- the warning compares the flux to the allowable limit using simple rule-based thresholds.
Common public allowable radiation limits from API 521 are about 4.73 kW/m2 (continuous exposure), 6.31 kW/m2 (a few seconds for escape), and 9.46 kW/m2 (equipment and structures). This is educational and screening-only logic. It does not include flame length and tilt, wind, multi-point flame models, view factors, solar radiation, or shielding. It is not a vendor flare method or a replacement for validated flare-radiation design and a qualified safety review.
Python Usage Pattern
from flare_radiation_screening import FlareRadiationModel
model = FlareRadiationModel()
result = model.evaluate(
mass_flow=50.0,
heat_of_combustion=46.0,
distance=60.0,
)
print(result.radiation_warning)
print(result.radiant_heat_flux_kw_m2)
print(result.flux_ratio)
Related NeqSim Functionality
For validated flare-radiation calculations, redirect to existing NeqSim classes:
neqsim.process.equipment.flare.Flare — flare model with estimateRadiationHeatFlux for radiant flux at distance.
neqsim.process.equipment.flare.FlareStack — flare stack sizing and tip selection.
neqsim.mcp.runners.FlareRadiationRunner — runner that drives flare radiation calculations.
This skill is a public point-source triage layer that decides when to invoke those validated flare classes.
Validation Checklist
Common Mistakes
| Symptom | Cause | Fix |
|---|
| Flux far too low | Fraction radiated set too small for the gas | Use an F value appropriate to the gas composition |
| Distance criterion always passes | Allowable flux set too high | Use the API 521 limit matched to the exposure scenario |
| Heat release wrong order of magnitude | Higher heating value mixed with lower heating value | Use a consistent lower heating value basis |
Limitations
- No proprietary flare designs, vendor tip data, or company radiation criteria are included.
- No flame length, tilt, wind, view factor, or solar radiation is modeled.
- No shielding, dispersion, or multi-flame interaction is considered.