| name | hvac-systems |
| description | HVAC systems — psychrometrics, cooling/heating load (ASHRAE), duct sizing (velocity/equal friction), fan selection, coil performance, refrigerant selection, VAV vs. CAV, DOAS, energy efficiency. |
| metadata | {"priority":7,"promptSignals":{"phrases":["HVAC","heating","cooling load","duct","psychrometric","fan selection","VAV","air handling","refrigerant","chiller"],"minScore":3}} |
HVAC Systems — Complete Skill
Psychrometrics
Key Properties (Moist Air)
Dry bulb temperature (T_db): thermometer reading [°C]
Wet bulb temperature (T_wb): evaporative cooling limit [°C]
Dew point (T_dp): temperature at which moisture condenses [°C]
Relative humidity (RH): φ = p_v / p_vs [%]
Humidity ratio: W = 0.622 × p_v / (p_atm - p_v) [kg_w/kg_da]
Specific enthalpy: h = 1.006 T_db + W(2501 + 1.86 T_db) [kJ/kg_da]
Saturation pressure:
p_vs = 0.6108 × exp(17.27 × T / (T + 237.3)) [kPa] (Magnus approximation, T in °C)
Psychrometric relations:
RH = W × p_atm / (0.622 + W) / p_vs
T_dp: solve p_v = p_vs(T_dp) for T_dp
T_wb ≈ T_db - (T_db - T_dp) / 3 (approximate)
Air density: ρ = p_atm / (R_da × T_K × (1 + 1.608 W)) ≈ 1.2 kg/m³ (standard conditions)
Psychrometric Processes
Sensible heating/cooling: horizontal line (W constant), T changes
Humidification: vertical line (T constant), W increases
Cooling and dehumidification: W decreases + T decreases (toward saturation curve)
Evaporative cooling: constant wet-bulb temperature line
Sensible heat ratio (SHR):
SHR = Q_sensible / Q_total = (Q_sensible) / (Q_sensible + Q_latent)
Typical office: SHR = 0.8-0.9; typical retail: 0.7-0.8
Cooling and Heating Loads
ASHRAE Load Methods
Peak cooling load components:
Q_total = Q_external + Q_internal + Q_ventilation
External:
Q_conduction = U × A × CLTD (Cooling Load Temperature Difference method)
Q_solar = SC × A × SHGF × CLF (Solar Heat Gain Factor × Cooling Load Factor)
Internal:
Q_people = N × (sensible gain/person + latent gain/person)
Q_lights = W_lights × 3.412 [BTU/hr/watt] × CLF_lights [ASHRAE Tables]
Q_equipment = Equipment wattage × CLF × diversity factor
Ventilation (OA):
Q_vent = ṁ_OA × Δh = 1.2 × V̇_OA × (h_outside - h_supply) [kW]
Simplified total:
Q_cooling [kW] = Σ all gains [kW]; then add safety factor (1.1-1.25)
Rule of thumb: ~100 W/m² (office), 150-200 W/m² (data center), 30-50 W/m² (residential)
Heating Load
Q_heating = Q_envelope + Q_infiltration - Q_internal
Q_envelope = U × A × ΔT (no solar credit for design day)
Q_infiltration = ṁ_inf × c_p × ΔT
ASHRAE 99% design dry bulb for winter (coldest 1% of hours)
Ventilation (ASHRAE 62.1)
V_oa = R_p × P_z + R_a × A_z
R_p = per-person ventilation rate [L/s/person]: 10 L/s/p (office)
R_a = per-area ventilation rate: 0.3 L/s/m² (office)
Zone efficiency E_z: varies by diffuser type (0.8-1.2)
Duct Design
Velocity Method
Select air velocity by duct location:
- Main trunk: 6-10 m/s (low-pressure); < 5 m/s (noise critical)
- Branches: 4-6 m/s
- Supply outlets: 2-3 m/s
From Q = V_duct × A: A = Q / V_duct → select rectangular or round duct
Equal Friction Method (Most Common)
Select friction loss per unit length: typically 0.8-1.0 Pa/m
Use Moody chart or duct friction chart (ASHRAE Fundamentals):
Δp/L = f × (ρ V²/2) / D_h
Colebrook-White (duct):
1/√f = -2 log(ε/(3.7D) + 2.51/(Re√f))
Duct roughness ε: galvanized steel = 0.15 mm, flex duct = 1.2 mm
Equivalent diameter (rectangular to circular):
D_eq = 1.30 × (a×b)^0.625 / (a+b)^0.25 (same hydraulic resistance)
Fitting losses: Σ K × ½ρV² (K from ASHRAE Handbook Fundamentals, Chapter 21)
Elbow K ≈ 0.2-0.5; tee main→branch K ≈ 0.5-1.5; entry K = 0.5
Pressure Drop Summary
Total system static pressure = friction losses + fitting losses
Fan must overcome: supply duct + return duct + coil + filters + diffusers
Fan Selection
Fan Laws
Q ∝ N, ΔP ∝ N², P_fan ∝ N³
Q ∝ D³, ΔP ∝ D², P ∝ D⁵ (same speed, different size)
Fan total efficiency:
η_t = Q × ΔP_t / P_shaft
Centrifugal forward-curved: η = 55-70%; backward-inclined: η = 70-82%; axial: η = 60-75%
Fan selection process:
- Calculate required Q [m³/s] and total static pressure [Pa]
- Select fan from manufacturer curve at operating point (intersection of system curve and fan curve)
- Check BHP; verify Q at SP matches design; check noise [dB]
Affinity laws for VFD speed control:
At 50% speed: Q = 50%, SP = 25%, P = 12.5% (cube law savings)
VFD payback: excellent for VAV systems with varying load
Coil Performance
Cooling Coil
Apparatus dew point (ADP) — temperature to which air must be cooled to reach desired conditions
Bypass factor (BF) = (T_leaving - T_ADP) / (T_entering - T_ADP)
BF = 0.05-0.20 (lower for more coil rows)
Coil capacity:
Q = ṁ_air × (h_in - h_out) [kW]
Coil rows: 6-8 rows for typical DX; 4-6 rows for chilled water
LMTD for coil:
LMTD = (ΔT₁ - ΔT₂) / ln(ΔT₁/ΔT₂)
ΔT₁ = entering air - leaving fluid
ΔT₂ = leaving air - entering fluid
Chiller Performance
COP = Q_evaporator / W_compressor
Chiller EER [BTU/hr/W] = COP × 3.412
IPLV (Integrated Part Load Value): weighted average at 100%, 75%, 50%, 25% load
Typical performance:
Air-cooled chiller: COP = 2.5-3.5 (full load)
Water-cooled centrifugal: COP = 5-7 (excellent)
VRF heat pump: COP = 3-5 (heating and cooling simultaneously)
System Types
VAV (Variable Air Volume) — Most Common Commercial
AHU maintains constant static pressure; VAV boxes modulate airflow
Supply temperature reset: raise T_supply when loads low (improves humidity control)
Minimum position: maintain minimum ventilation at low load
Energy savings: fan power reduces with cube of speed
CAV (Constant Air Volume)
Constant airflow; control by varying supply temperature
Simpler controls; higher fan energy at part load
Used: labs, clean rooms, areas requiring constant pressure control
DOAS (Dedicated Outdoor Air System)
Separate system handles 100% outdoor air ventilation; dehumidifies to neutral condition
Zone units (fan coils, VRF) handle sensible load only
Benefit: better humidity control; decoupled latent and sensible
VRF (Variable Refrigerant Flow)
Direct expansion system; one outdoor unit → multiple indoor units
Heat recovery VRF: simultaneous heating and cooling in different zones
Limitation: refrigerant pipe length limits (~100m equivalent); not suitable for all climates
Energy Efficiency
ASHRAE 90.1 Compliance
Envelope: U-values for wall, roof, glazing by climate zone
HVAC: minimum efficiencies for chillers (kW/ton), RTUs (EER), boilers (AFUE/Ec)
Lighting: LPD (W/m²) limits by space type
Energy Recovery
Heat wheel (rotary): 70-80% sensible + latent recovery
Plate HX: 60-75% sensible only
Runaround coil: 40-55%; useful for separated supply/exhaust streams
ASHRAE 90.1: ERV required when Q_oa > 70% of supply and building in most climate zones
Output
Provide: psychrometric state points (T_db, W, h) at all process endpoints, peak cooling load Q [kW] and heating load Q [kW], airflow Q [m³/s], duct size [mm] for given velocity/friction, fan total SP [Pa] and power [kW], chiller COP, refrigerant selection recommendation.