Heat Pipes & Vapor Chambers — Complete Skill
Operating Principle
Heat pipe cycle:
- Evaporator: heat input → liquid evaporates → vapor pressure rises
- Adiabatic section: vapor flows from evaporator to condenser (pressure gradient)
- Condenser: heat rejected → vapor condenses → liquid
- Return: liquid wicked back to evaporator by capillary pressure
Driving force: capillary pressure ΔP_cap = 2σ/r_eff (surface tension / effective pore radius)
Must overcome: vapor pressure drop + liquid pressure drop + gravity
Capillary Limit (Primary Operating Limit)
Capillary Pressure
Maximum capillary pressure: ΔP_cap,max = 2σ/r_eff
σ = fluid surface tension [N/m]
r_eff = effective pore radius of wick [m]
Effective pore radius by wick type:
Sintered powder: r_eff = 0.41 × r_particle (approximately)
Screen mesh: r_eff = 1/(2N) where N = mesh number [wires/m]
Groove: r_eff = w/2 (groove half-width)
Capillary limit (balance equation):
ΔP_cap,max ≥ ΔP_l + ΔP_v + ΔP_g
ΔP_l = liquid pressure drop in wick
ΔP_v = vapor pressure drop in vapor core
ΔP_g = gravitational head = ρ_l × g × L × sin(ψ) (ψ = tilt angle from horizontal)
Positive if condenser above evaporator (assists); negative if evaporator above (adverse)
Liquid Pressure Drop
ΔP_l = (μ_l × L_eff × Q) / (K × A_w × ρ_l × h_fg)
K = wick permeability [m²]
A_w = wick cross-section area [m²]
h_fg = latent heat of vaporization [J/kg]
L_eff = effective length = L_evap/2 + L_adiabatic + L_condenser/2
Wick permeability by type:
Sintered: K = r_particle² × (ε)³ / [37.5 × (1-ε)²] (Carman-Kozeny)
Screen mesh: K = d_wire²ε³ / [122(1-ε)²]
Groove (rectangular): K = w²(2h+w) / (4×f_Re×ν_l) (per groove, Hagen-Poiseuille)
Typical K: sintered Cu 10⁻¹² to 10⁻¹⁰ m²; grooved 10⁻¹⁰ to 10⁻⁸ m²
Vapor Pressure Drop
For low-temperature range (Ma << 1):
ΔP_v = (8μ_v × L_eff × Q) / (π r_v⁴ × ρ_v × h_fg)
r_v = vapor core radius
Vapor figure of merit: F_v = ρ_v × h_fg × σ / μ_v (higher = better vapor transport)
Liquid figure of merit: F_l = ρ_l × h_fg × K × σ / (μ_l × r_eff) (for wick transport)
Other Operating Limits
Sonic Limit
Vapor velocity becomes sonic at evaporator exit → choked flow → fixed Q
Q_sonic = A_v × (ρ_v × P_v × h_fg²) / (2T_v × R_v)^(1/2) / (γ_v × R_g)^(1/2)
Most relevant for liquid metal heat pipes at startup
Entrainment Limit
High vapor velocity → shear drags liquid droplets from wick surface → liquid depletion
Q_entrainment = A_v × h_fg × √(σ × ρ_v / (2π r_h))
r_h = hydraulic radius of wick surface element
Boiling Limit
Nucleate boiling inside wick → vapor bubbles block liquid flow
Q_boiling = 4π k_eff L T_v / h_fg ρ_v ln(r_i/r_v) × (2σ/r_n - ΔP_cap)
k_eff = effective thermal conductivity of saturated wick
Boiling limit particularly important for groove wicks and high heat flux
Flooding Limit (Gravity-Assisted, Thermosyphon)
Countercurrent liquid and vapor → flooding (liquid held up)
Q_flood = A_v × h_fg × [g σ ρ_l (ρ_l-ρ_v)/ρ_v²]^(1/4) × constant
Thermal Resistance Model
Equivalent Resistance Network
R_total = R_evap + R_wick,evap + R_vapor + R_wick,cond + R_cond
Evaporator contact (conduction through wall):
R_wall = t_wall / (k_wall × A_evap)
Wick thermal resistance:
R_wick = t_wick / (k_eff × A_wick)
k_eff (saturated screen wick): k_eff = k_l × [(k_l + k_s) - (1-ε)(k_l-k_s)] / [(k_l+k_s)+(1-ε)(k_l-k_s)]
ε = wick porosity; k_s = wick solid conductivity; k_l = liquid conductivity
Vapor space thermal resistance (very low for non-extreme conditions):
R_vapor ≈ T_v / (h_fg × ρ_v × A_v × Δv × ...) ≈ negligible for most applications
Overall (rule of thumb): R_total = 0.05 - 0.5°C/W (typical Cu-water, 20cm long)
Working Fluid Selection
Figure of Merit (Liquid Transport Factor)
N_l = ρ_l × σ × h_fg / μ_l [W/m²]
Higher = better heat transport capacity
Fluids and temperature ranges:
| Fluid | Range [°C] | N_l [W/m²] | Notes |
|---|
| Cryogens (N₂, NH₃) | -196 to -33 | Moderate | Cryocooling |
| Ammonia | -70 to 100 | 3×10¹⁰ | Excellent, toxic |
| Water | 30 to 200 | 4×10¹⁰ | Best for electronics |
| Methanol | -45 to 120 | 1×10¹⁰ | Low temp option |
| Acetone | -80 to 120 | 8×10⁹ | Al compatible |
| Mercury | 200 to 600 | 4×10¹¹ | High temp, toxic |
| Sodium | 400 to 1100 | 3×10¹² | Nuclear, aerospace |
Material Compatibility
Cu-Water: standard electronics (most common)
Al-Ammonia: space applications, lightweight
SS-Water: allowed but lower thermal conductivity wall
Incompatible: Al-Water (hydrogen generation), Cu-Acetone (corrosion)
Vapor Chamber
Design Characteristics
Flat plate heat pipe (2D spreading in XY plane)
Thicknesses: 2-6 mm total (electronics); up to 15mm (power electronics)
Effective conductivity: 10,000-50,000 W/mK (vs. 400 for Cu) — in-plane spreading
Application: CPU cooling, LED arrays, power electronics with multiple heat sources
Advantage over heat spreader: same or less weight, much higher effective conductivity
Sintered vs. Mesh Wick in Vapor Chamber
Sintered Cu: high capillary pressure, works against gravity; harder to fabricate
Mesh/Screen: easier fabrication; gravity dependent (must assist or horizontal)
Grooved: directional; best with gravity assist
Loop Heat Pipe (LHP)
Principle
Separate liquid and vapor lines; compensation chamber controls operating temperature
Evaporator: porous wick, fine pore (sintered Ni or Ti), small core
Condenser: parallel tubes or flat plate, remote from evaporator (up to 10m)
Startup: subcooling in compensation chamber must collapse to start circulation
Advantages over conventional heat pipe:
- Flexible tubing (remote evaporator → condenser)
- Works against gravity
- Lighter wick (only at evaporator)
- Used in: spacecraft thermal control (ISS, satellites), laptops (LG Gram)
Thermal resistance: R_LHP ≈ 0.02-0.2°C/W (depends on condenser)
Operating range: -40 to 120°C (ammonia); 20-120°C (water)
Output
Provide: heat transport capacity Q_max [W] at capillary limit, dominant limit identified (capillary/sonic/entrainment/boiling), thermal resistance R_total [°C/W], T_evaporator - T_condenser [°C], fluid selection recommendation, wick permeability K [m²], tilt sensitivity assessment (gravity assist/adverse).