| description | Self-heating, spontaneous ignition and thermal-criticality screening for reactive porous media — lagging fires from combustible liquid absorbed into porous thermal insulation, Frank-Kamenetskii and Semenov criticality, critical layer thickness, critical surface temperature, induction time to ignition, and Arrhenius parameter fitting from hot-storage (basket) tests per EN 15188 / ASTM E2021. USE WHEN: a task involves a flammable liquid leak or spill onto insulation or lagging, oil-soaked lagging, spontaneous combustion, self-ignition, smouldering, a fire with no obvious ignition source, insulation-material selection driven by absorbency, or fitting oxidation kinetics from oven/basket test data. Anchors on neqsim.process.safety.selfheating. |
| last_verified | 2026-08-07 |
| requires | {"java_packages":["neqsim.process.safety.selfheating","neqsim.process.safety.reaction"]} |
NeqSim Self-Heating and Spontaneous Ignition Skill
Screening for low-temperature self-heating leading to spontaneous ignition —
the mechanism behind lagging fires, where a combustible liquid soaks into porous
thermal insulation and ignites with no external ignition source.
When this skill applies
Reach for this skill when you see any of these signals:
- A fire or smoke event on insulated pipework, vessels or valves with no
identified ignition source.
- A leak of a combustible liquid — glycol (MEG/DEG/TEG), heat-transfer oil,
lubricating oil, hydraulic fluid, amine, diesel — onto or into porous
insulation (mineral wool, glass wool, calcium silicate, perlite).
- Questions phrased as "can this liquid self-ignite?", "is this insulation
safe?", "how thick can the lagging be?", "why did it catch fire hours
after the leak stopped?"
- A request to interpret oven / basket / hot-storage test results, or to
extrapolate small-scale test data to plant scale.
The one thing to get right
Self-heating is a size-dependent problem, not a temperature-only problem.
Heat is generated throughout the volume (scales with $r^3$) but lost through the
surface (scales with $r^2$). So the same material at the same temperature can be
perfectly stable as a thin film and ignite as a thick layer.
This is why the lumped adiabatic screening in
neqsim.process.safety.reaction.RunawayReactionAnalyzer cannot answer this
question — it assumes a well-stirred mass with no spatial conduction, so it has
no concept of a critical thickness or a critical surface temperature. Do not
substitute it. Use neqsim.process.safety.selfheating.
Equally, do not use a Gibbs/equilibrium calculation to decide whether something
self-ignites. GibbsReactor will report that any hydrocarbon is fully oxidised
to CO₂ and H₂O at 20 °C, because that is thermodynamically true and kinetically
irrelevant. Equilibrium gives you the fuel ($\Delta H$); only kinetics give you
the hazard.
Model selection
| Situation | Model | Class |
|---|
| Liquid absorbed in insulation, internal gradients matter (Bi ≫ 1) | Frank-Kamenetskii | PorousMediaSelfHeatingAnalyzer |
| Drained pool, thin film, small sample; uniform temperature (Bi ≪ 1) | Semenov | SemenovSelfHeatingAnalyzer |
| When will it ignite, not just whether | Transient 1-D conduction + Arrhenius source | SelfHeatingInductionSolver |
| Fitting E and P from oven test data | Linearised criticality regression | BasketTestRegression |
Governing relations
Frank-Kamenetskii criticality parameter:
$$
\delta = \frac{E,P,r^{2}}{\lambda,R,T_a^{2}}\exp!\left(-\frac{E}{R,T_a}\right)
$$
with $P = A,Q,\rho$ the volumetric heat-release pre-exponential factor [W/m³],
$E$ the activation energy [J/mol], $r$ the characteristic half-dimension [m],
$\lambda$ the effective conductivity of the wetted medium [W/(m·K)] and $T_a$
the boundary temperature [K]. A steady state exists only while
$\delta \le \delta_{crit}$, where $\delta_{crit}$ depends only on shape:
slab 0.878, infinite cylinder 2.00, sphere 3.32, cube 2.52, equicylinder 2.76.
Semenov criticality parameter, $\psi_{crit} = 1/e$:
$$
\psi = \frac{E,V,P}{h,S,R,T_a^{2}}\exp!\left(-\frac{E}{R,T_a}\right)
$$
Standard workflow
1. Get the kinetics — they are measured, never calculated
$E$ and $P$ cannot come from thermodynamics. Sources, in order of preference:
- Basket / hot-storage test on the actual soaked material →
BasketTestRegression.
- Published data for the same liquid/substrate pair.
- A screening estimate, clearly flagged as an assumption in
results.json.
BasketTestRegression fit = new BasketTestRegression();
fit.setEffectiveThermalConductivity(0.09);
fit.addPoint(SelfHeatingGeometry.CUBE, 25.0, "mm", 168.0, "C");
fit.addPoint(SelfHeatingGeometry.CUBE, 50.0, "mm", 149.0, "C");
fit.addPoint(SelfHeatingGeometry.CUBE, 100.0, "mm", 132.0, "C");
BasketTestRegressionResult k = fit.regress();
Require at least three basket sizes and check getRSquared() before trusting the fit.
2. Screen the plant-scale geometry
PorousMediaSelfHeatingResult r = k
.createAnalyzer(SelfHeatingGeometry.SLAB, 50.0, "mm", 180.0, "C")
.analyze();
r.getVerdict();
r.getCriticalTemperatureK();
r.getCriticalDimensionM();
For lagging on a hot line, use the convenience configuration, which applies a
conservative bounding assumption (slab half-dimension = full insulation thickness,
boundary temperature = pipe wall temperature) and records that assumption in
getWarnings():
new PorousMediaSelfHeatingAnalyzer()
.setEffectiveThermalConductivity(0.09)
.setActivationEnergy(110.0, "kJ/mol")
.setVolumetricHeatReleasePreFactor(5.0e13)
.forPipeInsulation(50.0, "mm", 180.0, "C")
.analyze();
3. If supercritical, get the induction time
SelfHeatingInductionResult t = new SelfHeatingInductionSolver()
.setGeometry(SelfHeatingGeometry.SLAB)
.setCharacteristicDimension(50.0, "mm")
.setEffectiveThermalConductivity(0.09)
.setBulkProperties(150.0, 1200.0)
.setActivationEnergy(110.0, "kJ/mol")
.setVolumetricHeatReleasePreFactor(5.0e13)
.setBoundaryTemperature(180.0, "C")
.setMaxTime(30.0, "day")
.solve();
t.isIgnited();
t.getInductionTimeHours();
4. Hand off the consequence
A predicted ignition is a source term, not the end of the study. Continue to
neqsim-consequence-analysis (pool/jet fire radiation) and
neqsim-relief-flare-network if the fire exposes pressurised equipment.
Input guidance and common mistakes
| Input | Guidance | Common mistake |
|---|
| $\lambda$ effective conductivity | Use the wetted composite value; absorbed liquid displaces pore air and raises it well above the dry rating | Using the dry insulation datasheet value — non-conservative |
| $r$ characteristic dimension | Must match SelfHeatingGeometry.getDimensionDescription() (half-thickness for a slab, radius for cylinder/sphere) | Passing full thickness where half-thickness is expected, or vice versa |
| $P$ pre-factor | $P = A,Q,\rho$ where $\rho$ is reactive liquid mass per bulk volume, not the insulation density | Using insulation bulk density instead of liquid loading |
| $T_a$ boundary temperature | The hot process surface, not ambient air, for lagging on a hot line | Using ambient air temperature — badly non-conservative |
| Geometry for transient solver | Only SLAB / INFINITE_CYLINDER / SPHERE are one-dimensional | Passing CUBE to SelfHeatingInductionSolver (rejected) |
Interpreting the verdict
SUBCRITICAL — a stable steady state exists. Still report the margin; the
steady self-heating excess is only a few kelvin, so there is no temperature
warning before runaway.
MARGINAL — within 30 % of criticality. Small changes in liquid loading,
thickness or surface temperature tip it over. Recommend confirmatory testing.
SELF_IGNITION — no steady state exists. Report the induction time and treat
as a credible fire scenario.
Reporting
Populate results.json with:
key_results: delta, delta_crit, critical_temperature_C,
critical_thickness_mm, induction_time_hours, verdict
assumptions: kinetic-parameter provenance (measured vs assumed), effective
conductivity basis, and the pipe-insulation bounding assumption if used
standards_applied: EN 15188, ASTM E2021 for the test method
- Carry every entry of
getWarnings() into the assumptions/gaps register
Mitigation hierarchy (for recommendations)
- Eliminate absorbency — closed-cell or non-absorbing insulation, so there is
no porous matrix to hold the liquid and trap the heat. This removes the
mechanism rather than managing it, and is normally the correct recommendation.
- Prevent wetting — eliminate the leak; fit liquid-tight cladding and
drainage that sheds leakage clear of the lagging.
- Reduce thickness below the critical dimension, or lower the surface
temperature below the critical temperature.
- Detect and inspect — remove and replace contaminated insulation promptly;
note that detection is weak as a sole barrier because the pre-runaway
temperature signature is only a few kelvin.
Related skills
neqsim-process-safety — HAZOP guideword Other than → self-ignition, LOPA, risk matrix
neqsim-consequence-analysis — fire radiation once ignition is predicted
neqsim-reaction-engineering — KineticReaction if a full reactor model of the oxidation is needed
neqsim-hazid-fmea-eta-fta — placing the scenario in an event tree
neqsim-standards-lookup — EN 15188, ASTM E2021, insulation standards