EnergyPlus existing-building calibration
Goal
Build an auditable EnergyPlus model aligned to measured energy, demand and operating behavior before DSM claims are made.
Calibration ladder
- Freeze measured-data period, timezone, interval semantics and weather source.
- Inventory known geometry, envelope, occupancy, HVAC topology, capacities, controls and meters; reconcile meter scope with modeled scope.
- Record source facts vs assumptions in a parameter/evidence ledger.
- Build the simplest model that preserves the real behavior required by the study.
- Match schedules and base loads before tuning efficiencies.
- Match seasonal/end-use behavior before chasing annual totals.
- Compare monthly and, where available, hourly/sub-hourly load shape and peak demand.
- Change a small documented parameter group per iteration; persist hashes and scorecards.
- Hold out a period when enough data exist.
When inheriting a campaign that failed its variability or physics gates, freeze
its model, weather, target, and result hashes as historical evidence. Audit
meter scope, operational telemetry, and structural mismatches before launching
more parameter search. A low annual bias caused by compensating end-use errors
is not a useful calibration starting point.
For a sparse-data seed, use a transparent defaults hierarchy and label every default. Do not use a passing monthly score to erase unsupported geometry, controls, fuel, or meter-allocation assumptions. A conventional tuning order is: meter scope/schedules and internal loads, geometry/envelope/infiltration, ventilation/fan/runtime, then plant/equipment performance and control behavior. If a change improves one fuel while materially degrading another, record the tradeoff rather than silently selecting by annual total.
Discrepancy-first control replay (learned on LBNL Building 59)
Before another envelope/load kWh sweep on a failed screening seed:
- Publish a measured-vs-IDF discrepancy table with severity labels
(
BLOCKING_TOPOLOGY, BLOCKING_CONTROL, BLOCKING_UNIT_BINDING, MAJOR,
PASS_ENGINE_ONLY).
- Do not retune topology blockers with continuous parameters. Missing UFT
fans, hydronic reheat, or a water plant require a new model lineage.
- A bounded CONTROL_REPLAY campaign may dial only evidence-backed control
and rating knobs (SAT setpoint, zone setpoints, OA minimum, DX capacity and
coil airflow inside the engine's rated domain). Label results
CONTROL_REPLAY_SCREENING_NOT_CALIBRATED even if monthly GL14 improves.
- Keep published equipment ratings that the proxy engine cannot accept (for
example 20,000 cfm vs TwoSpeedDX airflow/capacity domain) as evidence, not
as forced IDF inputs that crash or leave the rated domain.
- Parameterize hard-coded controls (e.g. SAT was once fixed at 14.4 °C /
57.9 °F while BAS medians were ~66–68 °F) before claiming “dialed in.”
- On PackagedVAV / zone-sizing proxies, keep
occupied_cooling_setpoint_c - supply_air_temperature_setpoint_c >= ~5.5 C
or EnergyPlus emits UpdateZoneSizing: Cooling supply air temperature within 5C of zone temperature warnings and fail-closed admission rejects
the run. Couple warmer measured-like SAT with a higher zone cooling SP on
the proxy; do not pretend the proxy UFAD topology matches the BAS.
- Never overwrite a hash-bound historical champion IDF; publish a new lineage
path and scorecard directory.
- After control replay, a separate LOAD_SCHEDULE dial-in may move MEL /
lighting W/m² and measured weekend/standby fractions from schedule priors.
Raise standby/weekend only together with density cuts — high standby at
champion W/m² inflates annual MEL. Label
LOAD_SCHEDULE_DIALIN_SCREENING_NOT_CALIBRATED. A full-year monthly GL14
numeric pass on a PackagedVAV proxy can still fail tuning/holdout and does
not authorize topology or DSM claims. Fan-pressure cuts that help CV(RMSE)
need measured fan-power binding before they become calibrated inputs.
Vibe 23 artifacts for this pattern:
config/b59_measured_vs_screening_idf.json
scorecards/b59_2020_screening/figures/measured_vs_idf/
scripts/run_b59_control_replay_30.py / vibe23.b59_control_replay
scripts/run_b59_load_schedule_dialin_24.py / vibe23.b59_load_schedule_dialin
config/b59_schedule_priors.json / docs/B59_LOAD_SCHEDULE_DIALIN_24_RESULTS.md
Default ASHRAE Guideline 14-style gates
- Monthly:
|NMBE| <= 5%, CV(RMSE) <= 15%.
- Hourly:
|NMBE| <= 10%, CV(RMSE) <= 30%.
Passing aggregate statistics does not prove every physical input is correct. Also inspect peak kW, time of peak, end uses, equipment runtime and zone temperatures.
Admit a run for scoring only after checking the EnergyPlus exit code, zero
warning/severe/fatal diagnostics (when that is the project's declared gate),
complete ancillary outputs, and the expected number of reporting intervals.
Do not call a repeatedly inspected period a blind holdout; label it a reserved
diagnostic slice and establish a new untouched period for validation.
Status ladder
MODEL_SEED · CALIBRATION_IN_PROGRESS · CONTROL_REPLAY_SCREENING · LOAD_SCHEDULE_DIALIN_SCREENING · MONTHLY_CALIBRATED · HOURLY_CALIBRATED · VALIDATED_HOLDOUT
CONTROL_REPLAY_SCREENING / LOAD_SCHEDULE_DIALIN_SCREENING mean discrepancy-
or evidence-driven knobs moved on an otherwise uncalibrated topology. They are
not calibration claims and do not unlock DSM.